English
Language : 

X80120 Datasheet, PDF (9/17 Pages) Intersil Corporation – Voltage Supervisor/Sequencer Dual Programmable Time Delay with Local/Remote Voltage Monitors
X80120, X80121
Manual Reset
The manual reset option allows a hardware reset of the
power sequencing pins. These can be used to recover the
system in the event of an abnormal operating condition.
Activating the MR pin for more than 5µs sets all of the
ViGDO outputs and the RESET output active (LOW). When
MR is released (and if all supplies are still at their proper
operating voltage) then the ViGDO and RESET pins will be
released after their programmed delay periods.
Dual Voltage Monitoring
X80120 monitors 2 voltage inputs. When the V1MON or
V4MON input is detected to be above the input threshold,
the respective output (V1GDO or V4GDO) goes inactive
(LOW). The ViGDO signal is de-asserted after a delay of
100ms. This delay can be changed on each ViGDO output
individually with bits in register CR3. The delay can be
100ms, 500ms, 1s and 5s. Each ViGDO signal remains
active until its associated ViMON input rises above the
threshold.
TABLE 2. ViGDO OUTPUT TIME DELAY OPTIONS
TiD1
0
TiD0
0
tDELAYi
100ms (default)
0
1
500ms
1
0
1 secs
1
1
5 secs
where i is the specific voltage monitor (i = 1, 4).
Fault Detection
The X80120 contains a Fault Detection Register (FDR) that
provides the user the status of the causes for a RESET pin
active (See Table 20).
At power-up, the FDR is defaulted to all “0”. The system
needs to initialize the register to 09h before the actual
monitoring can take place. In the event that any one of the
monitored sources fail, the corresponding bit in the register
changes from a “1” to a “0” to indicate the failure. When a
RESET is detected by the main controller, the controller
should read the FDR and note the cause of the fault. After
reading the register, the controller can reset the register bit
back to all “1” in preparation for future failure conditions.
Flexible Power Sequencing of Multiple Power
Supplies
The X80120 provides several circuits such as multiple
voltage monitors, programmable delays, and output drive
signals that can be used to set up flexible power monitoring
or sequencing schemes system power supplies. Below are
two examples:
1. Power Up of Supplies In Parallel Using Programmable
Delays. (See Figure 7 and Figure 8).
The X80120 monitors several power supplies, powered
by the same source voltage, that all begin power up at the
same time. Each voltage source is fed into the ViMON
inputs to the X80120. The ViMON inputs monitor the
voltage to make sure it has reached the minimum desired
level. When each voltage monitor determines that its
input is good, a counter starts. After the programmed
delay time, the X80120 sets the ViGDO signals LOW. The
ViGDO signals can be wire ORed together and tied to an
interrupt on the microcontroller. Any individual voltage
failure can be viewed in the Fault Detection Register.
In the factory default condition, each ViGDO output is
instructed to go LOW 100ms after the input voltage
reaches its threshold. However, each ViGDO delay is
individually selectable as 100ms, 500ms, 1s and 5s. The
delay times are charged via the SMBus during calibration
of the system.
Power
Supplies
5V
3.3V On/Off
1.2V On/Off
X80120/21
V4GDO
V4MON
V1GDO
V1MON
RESET
MR
µC
VCC1
IRQ RESET
FPGA
VCC1
VCC2
ASIC
VCC1
FIGURE 7. EXAMPLE APPLICATION OF PARALLEL POWER
CONTROL
2. Power Up of Supplies Via Relay Sequencing Using
Voltage Monitors (see Figure 9 and Figure 10).
Several power supplies and their respective power up
start times can be controlled using the X80120 such that
each of the power supplies will start in a relay sequencing
fashion. In the following example, the 1st supply is
allowed to power up when the input regulated supply
reaches an acceptable threshold. Subsequent supplies
power up after the prior supply has reached its operating
voltage. This configuration ensures that each subsequent
power supply turns on after the preceding supplies
voltage output is valid. Again, the X80120 offers
programmable delays for each voltage monitor and this
delay is selectable via the SMBus during calibration of the
system.
9
FN8151.0
January 20, 2005