PIDP-SS Datasheet, PDF (1/6 Pages) Gamewell-FCI by Honeywell – Monitor Modules with SmartScan
PIDP-SS, PID-SS,
CZI-SS, and DPID-SS
Monitor Modules with SmartScan™
Description
Four different monitor modules are
available for Gamewell intelligent con-
trols with SmartScan™ to suit a vari-
ety of applications. Monitor modules
are used to supervise an initiating de-
PIDP-SS
and
CZI-SS
vice circuit of dry-contact input de-
vices, such as conventional heat de-
tectors and pull stations, or monitor
and power a circuit of two-wire smoke
detectors (CZI-SS).
PIDP-SS — is a standard-sized mod-
ule (typically mounts to a 4" [10.16
cm] square box) that supervises ei-
ther a Style D (Class A) or Style B
(Class B) circuit of dry-contact input
g2465mod.tif
devices.
g2465duo.tif
PID-SS — is a miniature monitor
module (a mere 1.3" (3.302 cm) H x
2.75" (6.985 cm) W x 0.5" (1.270 cm)
D) used to supervise a Style B (Class
detail of
DPID-SS —
note “ones”
addresses are
0, 2, 4, 6, 8
only
B) circuit. Its compact design allows
the PID-SS to often be mounted in a
single-gang box behind the device it’s
monitoring.
CZI-SS — is a standard-sized mod-
ule used to monitor and supervise
compatible two-wire, 24 volt, smoke
detectors on a Style D (Class A) or
Style B (Class B) circuit.
DPID-SS — is a standard-sized dual monitor module used to monitor and supervise
two independent Style B (Class B) initiating device circuits (IDCs) at two separate,
consecutive addresses in intelligent, two-wire systems.
PIDP-SS Monitor Module
The PIDP-SS Monitor Module is intended for use in intelligent, two-wire systems,
where the individual address of each module is selected using the built-in rotary
switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Cir-
cuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module
has a panel-controlled LED indicator.
PIDP-SS Applications — Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-open dry-contact alarm
activation devices. May also be used to monitor normally-open supervisory devices
with special supervisory indication at the control panel. Monitored circuit may be
wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K
ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is re-
quired for supervision of the Style D circuit. Maximum IDC loop length is 2,500 ft./762
m (20 ohms maximum).
PIDP-SS Operation — Each PIDP-SS uses one of 99 available module addresses on
an SLC loop. It responds to regular polls from the control panel and reports its type
and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing
LED indicates that the module is in communication with the control panel. The LED
latches steady on alarm (subject to current limitations on the loop).
Features
PIDP-SS
• Built-in type identification automati-
cally identifies this device as a
monitor module to the control panel.
• Powered directly by two-wire SLC
loop. No additional power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates
for ease of wiring.
• Direct-dial entry of address: 01 –99
• LED flashes green during normal
operation (this is a programmable
option) and latches on steady red
to indicate alarm.
• Built-in type identification automati-
cally identifies this device as a
monitor module to the panel.
PID-SS
• Powered directly by two-wire FACP.
No additional power required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of
wiring.
• Direct-dial entry of address: 01 – 99
CZI-SS
• Supports compatible two-wire
smoke detectors.
• Supervises IDC wiring and connec-
tion of external power source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates
for ease of wiring.
• Direct-dial entry of address: 01 – 99
• LED flashes during normal opera-
tion (this is a programmable
option).
• LED latches steady to indicate
alarm on command from control
panel.
Listings
Listings and approvals below apply to
the basic PIDP-SS, PID-SS, CZI-SS
and DPID-SS monitor modules. In
some cases, certain modules may not
be listed by certain approval agencies,
or listing may be in process. Consult
factory for latest status.
• UL Listed: file S521.
• CSFM approved:
file 7300-1288:170.
PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06