English
Language : 

IC693MDL760 Datasheet, PDF (6/6 Pages) List of Unclassifed Manufacturers – Solenoid Valve Output Module
6
GFK-1881A
Solenoid Valve Output Module
Pneumatics Installation and Safety Requirements
Since the IC693MDL760 module’s internal valves exhaust inside the module, it is important that you
adhere to the following guidelines:
• Compressed air or other inert gas used in the module’s valves must be clean and dry. No water, oil,
or other contaminants can be tolerated in the air/gas stream. The presence of these will cause module
failure and possible damage to surrounding components.
• Only clean, dry, compressed air or inert gas may be used. Use of an explosive or flammable gas will
result in explosion or fire if used with this module.
• The module should not be used in an airtight, unvented cabinet. Use in an airtight cabinet could
result in the cabinet becoming pressurized, which could lead to personal injury and equipment
failure.
Compatibility
Warning
Failure to follow the above “Pneumatics Installation and Safety
Requirements” can result in personal injury, module failure, and
damage to associated equipment.
Hardware
This module is a standard size IC693 module, compatible with all IC693 series CPUs and baseplates. It
will function in any CPU, Expansion, or Remote baseplate.
Software
When configuring this module with VersaPro version 2.0 (or later version), it should be configured by its
catalog number. When configuring with programming software other than VersaPro version 2.0 (or later
version), the module must be configured as a standard 16-point generic output module.
Scan Time Contribution
This module has the same scan time contribution rating as a standard 16-point output module, as specified
in the I/O Scan Time Contribution tables in Chapter 2 of the IC693 PLC CPU Instruction Set Reference
Manual.