IC693MDL760 Datasheet, PDF (2/6 Pages) List of Unclassifed Manufacturers – Solenoid Valve Output Module
2
GFK-1881A
Solenoid Valve Output Module
Module Specifications
Table 1. Module Specifications
Module Specifications
Pneumatic Outputs
Outputs per Module
Thermal Derating
Supply Pressure
Pressure Drop
External Solenoid Power
Isolation
Solenoid Inrush Current
Solenoid Holding Current
ON Response Time
11 (grouped)
Refer to Table 2
100 psi max.
25 psi max.@ 0.25scfm
21.6-26.4VDC, 24VDC nominal
1500 volts between field side and logic side; 500 volts between
groups
33mA/valve @ 24VDC
13mA/valve @ 24VDC
12ms max.
OFF Response Time
Maximum Solenoid ON Time
Output Fitting
12ms max.
30 days max. (must be turned OFF at least once every 30 days)
Threaded for 10-32 adapter, 1/16″ hose barb provided
Supply Fitting
Threaded for 10-32 adapter, 1/8″ hose barb provided
LED Indicators for output points One LED per output point indicates ON/OFF state
LED “PWR” Indicator
LED indicates solenoid power is present
DC Outputs
Outputs per Module
Thermal Derating
Output Voltage
Isolation
Continuous Load Current
Inrush Current
Voltage Drop
Leakage Current
ON Response Time
OFF Response Time
Protection (each output)
LED Indicators
5 (grouped)
None
18-30VDC, 24VDC nominal
1500 volts between field side and logic side; 500 volts between
groups
0.5A @ 30VDC per point, 2.0A total for all five points
2.0A for 100ms
0.5V max
1mA @ 30VDC max
2ms max.
2ms max.
No internal fuse
One LED per output shows on/off state
Module Characteristics
Operational Ambient
Temperature
Backplane Current
45°C (113° F) max.
75mA from 5V bus (solenoid LEDs are powered from external
power source)