English
Language : 

IC693MDL760 Datasheet, PDF (4/6 Pages) List of Unclassifed Manufacturers – Solenoid Valve Output Module
4
GFK-1881A
Solenoid Valve Output Module
Field Wiring
Two AMP brand .025 square double-row .100 X .100 shrouded male pin headers provide the field connection to the five
24VDC discrete outputs and the Solenoid Forcing Pendent. These connectors have detent windows to retain the mating field
connector. The field connectors are not supplied with the module; however, the optional pendent comes with cable and
connector. See the next section, “Field Connectors,” for specifications.
Table 4. Pendent Connector Pin Assignments
Pin
Number*
1
2
3
4
5
6
7
8
9
10
11
12
Connection
Output Point 2 (Solenoid 2)
Output Point 4 (Solenoid 4)
Output Point 6 (Solenoid 6)
Output Point 8 (Solenoid 8)
Output Point 10 (Solenoid 10)
Output Point 11 (Solenoid 11)
Output Point 1 (Solenoid 1)
Output Point 3 (Solenoid 3)
Output Point 5 (Solenoid 5)
Output Point 7 (Solenoid 7)
Output Point 9 (Solenoid 9)
Solenoid Power Common
* Connector numbering was changed in version A of this data sheet
to meet a customer requirement. This did not involve any physical
changes to the module.
7
1
8
2
9
3
10
4
11
5
12
6
View: Looking at
Front of Module
Table 5. DC Output Connector Pin Assignments
Pin
Number*
1
2
3
4
5
6
7
8
9
10
Connection
External Solenoid Power COM
Output Point 15 (DC Output 4)
Field Power +24VDC (for DC Outputs)
Output Point 12 (DC Output 1)
Output Point 16 (DC Output 5)
External Solenoid Power +24VDC
N/C
Field Power Common (for DC Outputs)
Output Point 13 (DC Output 2)
Output Point 14 (DC Output 3)
* Connector numbering was changed in version A of this data sheet
to meet a customer requirement. This did not involve any physical
changes to the module.
6
1
7
2
8
3
9
4
10
5
View: Looking at
Front of Module