TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Assembly & Installation
The buffer module can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with input / output
terminal block at the top.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 3.1 Mounting
Snap on the DIN rail as shown in Fig. 3.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
Fig. 3.2 Dismounting
To uninstall, pull or slide down the latch with screw driver as
shown in Fig 3.2. Then slide the unit in the opposite direction,
release the latch and pull out the unit from the rail.
Safety Instructions
– ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
– To guarantee sufficient convection cooling, keep a distance of
50mm above and below the device as well as a lateral distance of
20mm to other units.
– Note that the enclosure of the device can become very hot depending
on the surrounding air temperature and load of the power supply. Risk
of burns!
– Only plug in and unplug connectors when power is turned off!
– DO NOT insert any objects into the unit.
– Hazardous voltages may be present for up to 5 minutes after the input
mains voltage is disconnected. Do not touch the unit during this time.
– The power supplies unit must be installed in an IP54 enclosure.
– The power supplies are built in units and must be installed in a cabinet
or room (condensation free environment and indoor location) that is
relatively free of conductive contaminants.
7
All parameters are specified at 25°C ambient unless otherwise noted.