TECHNICAL DATASHEET
CliQ M DIN Rail Power Supply
24V 120W 1 Phase / DRM-24V120W1PN
Mechanical
Case Cover / Chassis
Dimensions (L x W x D)
Unit Weight
Indicator
Cooling System
Terminal
Wire
Mounting Rail
Noise (1 Meter from power supply)
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test (Non-Operating)
Vibration (Non-Operating)
Bump Test (Operating)
Over Voltage Category
Pollution Degree
Input
Output
Input
Output
Aluminium
124 x 40 x 117 mm (4.88 x 1.57 x 4.61 inch)
0.63 kg (1.39 lb)
Green LED (DC OK) and Red LED (Overload)
Convection
3 Pins (Rated 300V/35A)
6 Pins (Rated 300V/28A)
AWG 18-8
AWG 22-12
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 40dBA
Operating
Storage
Vertical
Mounting
Horizontal
Mounting
-25°C to +70°C (Cold start -40°C)
-40°C to +85°C
> 60°C de-rate power by 2.5% / °C
> 50°C de-rate power by 2.5% / °C
5 to 95% RH (Non-Condensing)
0 to 5,000 Meters (16,400 ft.) for ITE application
0 to 2,500 Meters (8,200 ft.) for Industrial application
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
2 times per direction, 6 times in total
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
IEC 60068-2-29, 10G (100m/S²) for a duration of 11ms,
1,000 times per direction, 6,000 times in total
III
According to EN 50178 / EN 60204-1
(clearance and creepage distances) and
IEC 62103 (safety part)
2
5
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.