English
Language : 

DRM-24V120W1PN Datasheet, PDF (12/20 Pages) Delta Electronics, Inc. – Universal AC input voltage range
TECHNICAL DATASHEET
CliQ M DIN Rail Power Supply
24V 120W 1 Phase / DRM-24V120W1PN
Safety Instructions
 Vertical Mounting
 Horizontal Mounting
• An easily accessible disconnecting device shall be provided to disconnect the unit from the mains supply for servicing.
• Switch main power off before connecting or disconnecting the device. Risk of explosion!
• If the unit is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
• To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance
around the device.
Vertical Mounting: 40mm (1.57 inch) above and 20mm (0.79 inch) below the device as well as a lateral distance of 5mm
(0.2 inch) to other units. In case the adjacent device is a heat source, the lateral distance will be 15mm (0.6 inch).
Horizontal Mounting: 40mm (1.57 inch) above and below the device as well as a lateral distance of 20mm (0.79 inch) to
other units.
• The external enclosure where the unit will be installed shall meet the requirements for mechanical, electrical and fire enclosure.
• Note that the enclosure of the device can become very hot depending on the ambient temperature and load of the power supply.
Risk of burns!
• The main power must be turned off before connecting or disconnecting wires to the terminals.
• DO NOT insert any objects into the unit.
• Dangerous voltages present for at least 5 minutes after disconnected wires to the terminals.
• The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor
location) that is relatively free of conductive contaminants.
12
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 01)