English
Language : 

AA3-B0-10-450-1B1-C Datasheet, PDF (8/24 Pages) Carling Technologies – Circuit Breaker
8 | A-Series Handle WORLD – Ordering Scheme
A
1
Series
A
2
Actuator
3
3
Poles
—B
4
Circuit
0 — 14 — 450 — 1
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
A
9
Actuator
Color
1—P
10
Mounting/
Barriers
11
Agency
Approval
1 SERIES
A
2 ACTUATOR1
A Handle, one per pole
B Handle, one per multi-pole unit
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
3 POLES
1
One
2
Two
3
Three
4
Four
5
Five
6
Six
8 TERMINAL9
110 Push-On 0.250 Tab (Q.C.)
2
Screw 8-32 w/upturned lugs
311 Screw 8-32 (Bus Type)
4
Screw 10-32 w/upturned lugs
511 Screw 10-32 (Bus Type)
6
Screw 8-32 w/upturned lugs
and 30° bend
7
Screw 8-32 (Bus Type) and
30° bend
8
Screw 10-32 w/upturned lugs
and 30° bend
9
Screw 10-32 (Bus Type) and
30° bend
B Screw M5 w/upturned lugs
C Screw M4 w/upturned lugs
E11 Screw M4 (Bus Type)
F Screw M5 w/upturned lugs
and 30° bend
G Screw M5 (Bus Type)
and 30° bend
H11 Screw M5 (Bus Type)
R Screw M4 w/upturned lugs
and 30° bend
T11 Screw M4 (Bus Type)
and 30° bend
4 CIRCUIT
A2 Switch Only (No Coil)
B Series Trip (Current)
C Series Trip (Voltage)
5 AUXILIARY/ALARM SWITCH5
0
w/o Aux Switch
2
S.P.D.T., 0.110 Q.C. Term.
3
S.P.D.T., 0.139 Solder Lug
D3 Shunt Trip (Current)
E3 Shunt Trip (Voltage)
H3,4 Dual Coil with Shunt Trip
Voltage Coil
4
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
9 ACTUATOR COLOR & LEGEND
Acuator Color
I-O
Dual
White
A
1
Black
C
2
Red
F
3
Green
H
4
Blue
K
5
Yellow
M
6
Gray
P
7
Orange
R
8
Legend Color
Black
White
White
White
White
Black
Black
Black
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
427 50/60Hz Short, Hi-Inrush
447 50/60Hz Medium, Hi-Inrush
467 50/60Hz Long, Hi-Inrush
527 DC, Short,Hi-Inrush
547 DC, Medium, Hi-Inrush
567 DC, Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100
285 0.850
215 0.150
290 0.900
220 0.200
295 0.950
225 0.250
410 1.000
230 0.300
512 1.250
235 0.350
415 1.500
240 0.400
517 1.750
245 0.450
420 2.000
250 0.500
522 2.250
255 0.550
527 2.750
260 0.600
430 3.000
265 0.650
435 3.500
270 0.700
440 4.000
275 0.750
445 4.500
280 0.800
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)6
CODE
A06
A12
A18
A24
AMPERES
6 DC
12 DC
18 DC
24 DC
A32 32 DC
A48 48 DC
A65 65 DC
J06 6 AC
J12 12 AC
J18 18 AC
J24 24 AC
J48 48 AC
613
614
615
616
617
618
620
622
624
625
630
6358
6408
6458
6508
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
45.000
50.000
J65 65 AC
K20 120 AC
L40 240 AC
10 MOUNTING/BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1
6-32 x 0.195 inches
no
A
6-32 x 0.195 inches
yes
2
ISO M3 x 5mm
no
B
ISO M3 x 5mm (multipole only)
yes
Front panel Snap-In, 0.75” wide bezel
5
without Handleguard no
6
without Handleguard (multipole only)
yes
Front panel Snap-In, 0.96” wide bezel
7
without Handleguard, 1-pole 0.96” wide;
no
multipole units have .105” bezel overhang on all sides
8
without Handleguard, 1-pole 0.96” wide;
yes
(multipole only) .105” bezel overhang on all sides
11 AGENCY APPROVAL
P TUV Certified, UL Recognized & CSA Accepted
Q UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit
codes B, C, D, E, and H.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a
protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select Current Code 630.
For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require
30VA minimum power to trip and are rated for intermittent duty only.
5 On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10, 20 & 30.
7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA
Accepted & TUV Certified to 50 amps.
8 Available up to two poles with AC or DC delays.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G and H.
10 Terminal Code 1: TUV Certification up to 30 amps, but not recommended over 20 amps.
11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers.
These breakers are only TUV Certified when the washers are used.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com