AN1003
Application Notes
HALF WAVE
θ
1.8
1.6
Peak Voltage
1.4
1.2
1.0
RMS
0.8
Power
0.6
0.4
0.2
AVG
0
0 20 40 60 80 100 120 140 160 180
Conduction Angle (θ)
Figure AN1003.3 Half-Wave Phase Control (Sinusoidal)
θ
FULL WAVE
θ
1.8
1.6
Peak Voltage
1.4
1.2
RMS
1.0
Power
0.8
0.6
0.4
AVG
0.2
0
0 20 40 60 80 100 120 140 160 180
Conduction Angle (θ)
Figure AN1003.4 Symmetrical Full-Wave Phase Control (Sinusoidal)
Figure AN1003.3 and Figure AN1003.4 also show the relative
power curve for constant impedance loads such as heaters.
Because the relative impedance of incandescent lamps and
motors change with applied voltage, they do not follow this curve
precisely. To use the curves, find the full-wave rated power of the
load, and then multiply by the ratio associated with the specific
phase angle. Thus, a 180° conduction angle in a half-wave circuit
provides 0.5 x full-wave conduction power.
In a full-wave circuit, a conduction angle of 150° provides 97%
full power while a conduction angle of 30° provides only 3% of full
power control. Therefore, it is usually pointless to obtain conduc-
tion angles less than 30° or greater than 150°.
Figure AN1003.5 and Figure AN1003.6 give convenient direct
output voltage readings for 115 V/230 V input voltage. These
curves also apply to current in a resistive circuit.
Input
Voltage
230 V 115 V
360 180
θ HALF WAVE
320 160
280 140
Peak Voltage
240 120
200 100
160 80
RMS
120 60
80 40
40 20
AVG
00
0 20 40 60 80 100 120 140 160 180
Conduction Angle (θ)
Figure AN1003.5 Output Voltage of Half-wave Phase
θ
Input
Voltage
230 V 115 V
360 180
FULL WAVE
θ
320 160
280 140
Peak Voltage
240 120
200 100
RMS
160 80
120 60
AVG
80 40
40 20
00
0 20 40 60 80 100 120 140 160 180
Conduction Angle (θ)
Figure AN1003.6 Output Voltage of Full-wave Phase Control