English
Language : 

PIRD20.241 Datasheet, PDF (8/15 Pages) PULS GmbH – DC 12-28V, 20A, DUAL INPUT REDUNDANCY MODULE
PIANO-Series
PIRD20.241
DC 12-28V, 20A, DUAL INPUT REDUNDANCY MODULE
9. EMC
The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions.
EMC Immunity
According to generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2 Contact discharge
8kV
Criterion A
on indirect coupling plane
Air discharge
15kV
Criterion A
Electromagnetic RF field
EN 61000-4-3 80MHz-2.7GHz
20V/m
Criterion A
Fast transients (Burst)
Surge voltage on input lines
EN 61000-4-4
EN 61000-4-5
Surge voltage on output lines EN 61000-4-5
Input lines
Output lines
+Æ-
+/- Æ earthed DIN-rail
+Æ-
+/- Æ earthed DIN-rail
2kV
2kV
500V
1kV
500V
1kV
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Conducted disturbance on
input lines
EN 61000-4-6 0.15-80MHz
20V
Criterion A
Conducted disturbance on
output lines
EN 61000-4-6 0.15-80MHz
20V
Criterion A
Power-frequency magnetic
field 1)
EN 61000-4-8 50Hz
30A/m
Criterion A
Criterions:
A: Redundancy module shows normal operation behavior within the defined limits.
Notes:
1) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission 4)
According to generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
input lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power ports according EN
61000-6-3 fulfilled 2) 3)
Conducted emission
output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power ports according EN
61000-6-3 fulfilled 2) 3)
Radiated emission
EN 55011, EN 55022
Class B 2)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Notes:
2) Provided, that power sources connected on the inputs fulfill the class B requirements too.
3) Provided, that power sources connected on the inputs fulfill the requirements too.
4) The redundancy module incorporates only diodes and no RF-generating circuits and does not contribute to EMC emissions.
Sep. 2016 / Rev. 1.0 DS-PIRD20.241
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany