English
Language : 

PIRD20.241 Datasheet, PDF (6/15 Pages) PULS GmbH – DC 12-28V, 20A, DUAL INPUT REDUNDANCY MODULE
PIANO-Series
PIRD20.241
DC 12-28V, 20A, DUAL INPUT REDUNDANCY MODULE
6. TERMINALS AND WIRING
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Type
Solid wire
Stranded wire
American Wire Gauge
Max. wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
screw terminals
max. 6mm2
max. 4mm2
AWG20-10
2.8mm (including ferrules)
7mm / 0.28inch
3.5mm slotted or cross-head No 2
1Nm, 9lb.in
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
75°C for ambient up to 55°C minimum and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.
7. FUNCTIONAL DIAGRAM
+
Input 1
-
+
Input 2
-
Fig. 7-1 Functional diagram
Surge
Protection
Surge
Protection
+
Output
-
Surge
Protection
-
Sep. 2016 / Rev. 1.0 DS-PIRD20.241
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
6/15