English
Language : 

PIRD20.241 Datasheet, PDF (4/15 Pages) PULS GmbH – DC 12-28V, 20A, DUAL INPUT REDUNDANCY MODULE
PIANO-Series
PIRD20.241
DC 12-28V, 20A, DUAL INPUT REDUNDANCY MODULE
3. INPUT AND OUTPUT CHARACTERISTICS
Number of inputs
-
2
Number of outputs
-
1
Input voltage
nom. DC 12-28V ±25%
Input voltage range
-
9-35Vdc
Voltage drop, input to output typ. 0.46V
at 2x5A, see Fig. 3-1
typ. 0.56V
at 2x10A, see Fig. 3-1
Input current
nom. 2x 0-10A
continuous
nom. 2x 10-16A
for 5 seconds
Peak input current
max. 1000A
for maximal 10ms per input
Output current
nom. 20A
continuous
nom. 20-32A
for 5 seconds
max. 26A *)
at continuous overload or short circuit
Reverse current
max. 4mA
per input, -40°C to +70°C
Reverse voltage
max. 45Vdc
voltage applied to the output, continuously allowed
*) Ensure that the continuous output current does not exceed 26A. Check the short-circuit current of the power sources and if the power
source can deliver more than 26A together, use an appropriate fuse on the output.
Fig. 3-1 Input to output voltage drop
Voltage Drop, typ.
600mV
500mV
400mV
300mV
200mV
100mV
Output: 0
Input: 0
A
B
A... 25°C
B... 60°C
Input, Output Current
5A 10A 15A 20A
2x2.5A 2x5A 2x7.5A 2x10A
Fig. 3-2 Test setup for voltage drop measurements
PIC120.241x or
PIC240.241x
24V, 5A or +
24V, 10A
-
I1
A
V U1
PIRD20.241
Input 1
Output
Output
IOUT
A
UOUT V
Variable
Load,
0-20A
PIC120.241x or
PIC240.241x
24V, 5A or +
24V, 10A
-
I2
A
V U2
Input 2
I1 = I2
U1 = U2
Voltage Drop = U1 - UOUT
Sep. 2016 / Rev. 1.0 DS-PIRD20.241
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
4/15