CS3.241 Datasheet, PDF (8/24 Pages) PULS GmbH – SINGLE PHASE INPUT
C-Line
CS3.241
24V, 3.3A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
typ.
min.
typ.
min.
AC 100V
38ms
29ms
19ms
15ms
AC 120V
60ms
45ms
29ms
23ms
AC 230V
244ms
200ms
120ms
95ms
at 24V, 1.65A, see Fig. 7-1
at 24V, 1.65A, see Fig. 7-1
at 24V, 3.3A, see Fig. 7-1
at 24V, 3.3A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
225ms
200
175
150
Hold-up
Time
24V, 1.65A, min.
24V, 1.65A, typ.
125
100
75
50
24V, 3.3A, min.
25
24V, 3.3A, typ.
Input Voltage
0
85 120 155 190 230Vac
Fig. 7-2 Shut-down behavior, definitions
Input
Voltage
Zero Transition
Output
Voltage
Hold-up Time
- 5%
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.