24V, 3.3A, SINGLE PHASE INPUT
15. PROTECTION FEATURES
Output protection
Electronically protected against overload, no-load and short-circuits*)
Output over-voltage protection typ. 34Vdc
max. 39Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Caution: For use in a controlled environment according
to CSA 22.2 No 107.1-01.
Penetration protection
> 3.5mm
e.g. screws, small parts
Over-temperature protection
no
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
included
not user replaceable
*) In case of a protection event, audible noise may occur.
16. SAFETY FEATURES
Input / output separation*)
Class of protection
Isolation resistance
PE resistance
Touch current (leakage current)
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
I
PE (Protective Earth) connection required
> 5MOhm
input to output, 500Vdc
< 0.1Ohm
between housing and PE terminal
typ. 0.16mA / 0.35mA
100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.24mA / 0.52mA
120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.41mA / 0.85mA
230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.22mA / 0.43mA
110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.32mA / 0.63mA
132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.57mA / 1.08mA
264Vac, 50Hz, TN-,TT-mains / IT-mains
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/24