24V, 3.3A, SINGLE PHASE INPUT
5. INPUT INRUSH CURRENT
After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input
inrush current is generated.
The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
max.
typ.
typ.
max.
AC 100V
24Apeak
14Apeak
20Apeak
0.4A2s
AC 120V
28Apeak
16Apeak
23Apeak
0.5A2s
AC 230V
54Apeak
32Apeak
45Apeak
1.7A2s
at +40°C ambient, cold start
at +25°C ambient, cold start
at +40°C ambient, cold start
at +40°C ambient, cold start
Fig. 5-1 Typical input inrush current behavior
Input Current
Input Voltage
Output Voltage
Input:
Output:
Ambient:
230Vac
24V, 3.3A
25°C
Upper curve: Input current (20A / DIV)
Medium curve: Input voltage (500V / DIV)
Lower curve: Output voltage (20V / DIV)
Time scale: 40ms / DIV
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/24