English
Language : 

CS3.241 Datasheet, PDF (7/24 Pages) PULS GmbH – SINGLE PHASE INPUT
C-Line
CS3.241
24V, 3.3A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage
nom. 24V
Adjustment range
min. 24-28V
guaranteed
max. 30V**)
at clockwise end position of potentiometer
Factory settings
typ. 24.1V
±0.2%, at full load, cold unit,
Line regulation
Load regulation
max. 50mV
max. 100mV
90-300Vac
static value, 0A Æ 3.3A; see Fig. 6-1
Ripple and noise voltage
max. 50mVpp
20Hz to 20MHz, 50Ohm
Output current
nom. 3.3A
at 24V, ambient temperature <60°C, see Fig. 6-1
nom. 2.5A
at 24V and 70°C ambient temperature
nom. 2.7A
at 28V, ambient temperature <60°C, see Fig. 6-1
nom. 2.1A
at 28V and 70°C ambient temperature
Reduce output current linearly between +60°C and +70°C
Output power
nom. 80W
continuously available
Overload behavior
continuous current see Fig. 6-1
Short-circuit current
min. 4A*)
load impedance <250mOhm, see Fig. 6-1
max. 8A*)
load impedance <250mOhm, see Fig. 6-1
Output capacitance
typ. 1 450μF
included inside the power supply
*)
Discharge current of output capacitors is not included.
**) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 28.5V.
Fig. 6-1 Output voltage vs. output current,
typ.
Output Voltage
28V
24
20
Adjustment
Range
a) 100Vac
b) 120Vac
c) 230Vac
16
c
ba
12
8
4
Output Current
0
0 1 2 3 4 5 6 7A
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/24