CS10.244 Datasheet, PDF (8/24 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.244
24V, 10A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
typ.
min.
typ.
min.
typ.
min.
102ms
81ms
45ms
36ms
36ms
27ms
at 230Vac, 24V, 5A, see Fig. 7-1
at 230Vac, 24V, 5A, see Fig. 7-1
at 230Vac, 24V, 10A, see Fig. 7-1
at 230Vac, 24V, 10A, see Fig. 7-1
at 230Vac, 24V, 12A, see Fig. 7-1
at 230Vac, 24V, 12A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
120ms
a) 24V 5A typ.
b) 24V 5A min.
100
c) 24V 10A typ.
d) 24V 10A min.
80 e) 24V 12A min.
60
40
20
0
170
200
a
b
c
d
e
Input Voltage
230
264Vac
Input
Voltage
Output
Voltage
Zero Transition
Hold-up Time
- 5%
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS10.244-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/24