English
Language : 

CS10.244 Datasheet, PDF (23/24 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.244
24V, 10A, SINGLE PHASE INPUT
22.9. CHARGING OF BATTERIES
The power supply shall not be used to charge batteries. Choose power supplies of the QP-Series or CP-Series for
charging batteries.
22.10.OPERATION ON TWO PHASES
The power supply can also be used on two-phases of a three-phase-system. A
L1
phase-to-phase connection is allowed as long as the supplying voltage is
below 240V+10%.
L3
L2
Power Supply
AC
internal
L fuse
Fuse N
PE
DC
22.11.USE IN A TIGHTLY SEALED ENCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
Enclosure:
Load:
Input:
Temperature inside enclosure:
Temperature outside enclosure:
Temperature rise:
Rittal Typ IP66 Box PK 9519 100, plastic, 180x180x165mm
24V, 8A; (=80%) load is placed outside the box
230Vac
49.7°C (in the middle of the right side of the power supply with a distance of 2cm)
23.0°C
26.7K
Jul. 2015 / Rev. 2.0 DS-CS10.244-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
23/24