CS10.244 Datasheet, PDF (5/24 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.244
24V, 10A, SINGLE PHASE INPUT
3. AC-INPUT
AC input
nom. AC 200-240V
±10%
Mains network systems
TN, TT or IT
AC input range
min. 180-264Vac
264-300Vac
continuous operation,
max. 500ms
Allowed voltage L or N to earth max. 300Vac
continuous, IEC 62103
Input frequency
nom. 50–60Hz
±6%
Turn-on voltage
typ. 155Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ. 137Vac
steady-state value, see Fig. 3-1
Input current
typ. 2.2A
at 230Vac, 24V, 10A, see Fig. 3-3
Power factor*)
typ. 0.52
at 230Vac, 24V, 10A, see Fig. 3-4
Crest factor**)
typ. 3.2
at 230Vac, 24V, 10A
Start-up delay
typ. 220ms
see Fig. 3-2
Rise time
typ. 35ms
at 230Vac, 24V, 10A const. current load, 0mF load
capacitance, see Fig. 3-2
typ. 75ms
at 230Vac, 24V, 10A const. current load, 10mF load
capacitance,, see Fig. 3-2
Turn-on overshoot
max. 100mV
see Fig. 3-2
External input protection
See recommendations in chapter 22.3.
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage ranges
POUT
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
Rated Input
Range
VIN
180
264 300Vac
Fig. 3-3 Input current vs. output load at 24V
Input Current, typ.
3A
2.5
2.0
1.5
1.0
0.5
Output Current
0
2 3 4 5 6 7 8 9 10 11 12A
Output
Voltage
- 5%
Start-up Rise
delay Time
Fig. 3-4 Power factor vs. output load
Power Factor, typ.
0.65
0.60
0.55
0.50
0.45
0.40
0.35
Output Current
2 3 4 5 6 7 8 9 10 11 12A
Jul. 2015 / Rev. 2.0 DS-CS10.244-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/24