English
Language : 

CS10.244 Datasheet, PDF (6/24 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.244
24V, 10A, SINGLE PHASE INPUT
4. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the QS10.241 or CP10.241 unit instead.
5. INPUT INRUSH CURRENT
A NTC inrush limitation circuit limits the input inrush current after turn-on of the input voltage.
The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
max.
typ.
max.
59Apeak
48Apeak
3A2s
at 230Vac, +40°C ambient, cold start
at 230Vac, +40°C ambient, cold start
at 230Vac, +40°C ambient, cold start
Fig. 5-1 Typical input inrush current behavior
1>
2>
Input:
Output:
Ambient:
230Vac
24V, 10A
+40°C
Upper curve: Input current (20A / DIV)
Medium curve: Input voltage (200V / DIV)
Lower curve: Output voltage (10V / DIV)
Time scale: 20ms / DIV
3 >3
Jul. 2015 / Rev. 2.0 DS-CS10.244-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/24