English
Language : 

CS10.243 Datasheet, PDF (8/25 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.243
24V, 10A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
typ.
min.
typ.
min.
typ.
min.
AC 100V
62ms
50ms
23ms
19ms
17ms
14ms
AC 120V
107ms
86ms
46ms
37ms
35ms
28ms
at 24V, 5A, see Fig. 7-1
at 24V, 5A, see Fig. 7-1
at 24V, 10A, see Fig. 7-1
at 24V, 10A, see Fig. 7-1
at 24V, 12A, see Fig. 7-1
at 24V, 12A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
120ms
100
80
a) 24V 5A typ.
b) 24V 5A min.
c) 24V 10A typ.
d) 24V 10A min.
e) 24V 12A min.
a
b
60
c
d
40
e
20
0
85
Input Voltage
100
120 132Vac
Input
Voltage
Output
Voltage
Zero Transition
Hold-up Time
- 5%
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS10.243-EN
All parameters are specified at 24V, 10A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/25