English
Language : 

CS10.243 Datasheet, PDF (11/25 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.243
24V, 10A, SINGLE PHASE INPUT
11. TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Type
Solid wire
Stranded wire
American Wire Gauge
Max. wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
Pull-out force
Screw terminals
0.5-6mm2
0.5-4mm2
AWG20-10
2.8mm (including ferrules)
7mm / 0.28inch
3.5mm slotted or cross-head No 2
1Nm, 9lb.in
according to UL 486E
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
Jul. 2015 / Rev. 2.0 DS-CS10.243-EN
All parameters are specified at 24V, 10A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/25