CS10.243 Datasheet, PDF (4/25 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT
C-Line
CS10.243
24V, 10A, SINGLE PHASE INPUT
3. AC-INPUT
AC input
Mains network systems
AC input range
Allowed voltage L or N to earth
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
nom. AC 100-120V
±10%
TN, TT or IT
min.
90-132Vac
85-90Vac
132-150Vac
continuous operation
short-tem or with reduced output current
max. 500ms
max. 300Vac
continuous, IEC 62103
nom. 50–60Hz
±6%
typ. 82Vac
steady-state value, see Fig. 3-1
typ. 78Vac
steady-state value, see Fig. 3-1
See recommendations in chapter 22.3.
AC 100V
AC 120V
Input current
typ.
4.32A
3.71A
at 24V, 10A, see Fig. 3-3
Power factor*)
typ.
0.61
0.59
at 24V, 10A, see Fig. 3-4
Crest factor**)
typ.
2.6
2.8
at 24V, 10A
Start-up delay
typ.
250ms
215ms
see Fig. 3-2
Rise time
typ.
35ms
35ms
at 24V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
typ.
75ms
75ms
at 24V, 10A const. current load,
10mF load capacitance,, see Fig. 3-2
Turn-on overshoot
max.
100mV
100mV
see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage ranges
POUT
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
Rated Input
Range
(85) 90
VIN
132 150Vac
Output
Voltage
- 5%
Start-up Rise
delay Time
Jul. 2015 / Rev. 2.0 DS-CS10.243-EN
All parameters are specified at 24V, 10A, 120Vac, 60Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/25