English
Language : 

YR40.241 Datasheet, PDF (7/17 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR40.241
12-28V, 40A, DUAL REDUNDANCY MODULE
6. TERMINALS AND WIRING
Type
Solid wire
Stranded wire
American Wire Gauge
Max. wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
Input
Screw termination
IP20 Finger safe construction.
Suitable for field installation.
0.5-6mm2
0.5-4mm2
20-10 AWG
2.8mm (including ferrule)
7mm / 0.275inch
3.5mm slotted or Pozidrive No 2
0.8Nm, 7lb.in
Output
Screw termination
IP20 Finger safe construction.
Suitable for field installation.
0.5-16mm2
0.5-10mm2
22-8 AWG
5.2mm (including ferrule)
12mm / 0.5inch
3.5mm slotted or Pozidrive No 2
1.2Nm, 10.6lb.in
To connect the chassis to ground, use a ring-type terminal (ring cable lug) which is suitable for a M4 screw and connect
it to the chassis ground terminal on top of the unit.
Instructions:
a) The external circuitry of all terminals must meet the safety requirements stipulated by IEC/EN/UL 60950-1: SELV.
b) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
c) Follow national installation codes and installation regulations!
d) Ensure that all strands of a stranded wire enter the terminal connection!
e) Screws of unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
g) Do not connect or disconnect the wires from the terminals below -25°C (-13°F).
Feb. 2014 / Rev. 1.3 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
7/17