YR40.241 Datasheet, PDF (4/17 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR40.241
12-28V, 40A, DUAL REDUNDANCY MODULE
3. INPUT AND OUTPUT CHARACTERISTICS
Number of inputs
-
2
Number of outputs
-
1
Input voltage
nom. DC 12-28V ±30% The input circuitry must meet the SELV requirements
stipulated by IEC/EN/UL 60950-1.
Input voltage range
-
8.4-36.4Vdc
Voltage drop, input to output typ. 140mV
at 2x20A, see Fig. 3-1
typ. 72mV
at 2x10A, see Fig. 3-1
typ. 112mV
at 1x20A, see Fig. 3-2
Input current
nom. 2x 0-20A
continuous
nom. 2x 20-32.5A
for 5 seconds
max 2x 32.5A
at continuous overload or short circuit
Peak input current
max. 1000A
for max. 1ms per input
Output current
nom. 40A
continuous
nom. 40-65A
for 5 seconds
max. 65A
at continuous overload or short circuit
Reverse current
max. 1mA
at 24V, per input, -40°C to +70°C
Reverse voltage
max. 40Vdc
voltage applied to the output, continuously allowed
Output capacitance
typ. 320μF
Note:
Ensure that the continuous output current does not exceed 65A. Check the short-circuit current of the power sources and if the
power source can deliver more than 65A together, use an appropriate fuse on the output.
Fig. 3-1 Input to output voltage drop when both inputs draw current
(typical 1+1 redundant case, when the output voltages of the two units are equal)
Voltage Drop, typ
160mV
140mV
120mV
100mV
A... 25°C
B... 60°C
BA
80mV
60mV
40mV
20mV
0mV
Input / Output Current
Output: 0
Input: 0
10A 20A 30A 40A
2x5A 2x10A 2x15A 2x20A
QS/QT20
24V,20A
+
-
I1
A
V U1
YR40
Input 1
QS/QT20
24V,20A
+
-
I2
A
V U2
Input 2
I1 = I2
U1 = U2
Output
Output
IOUT
A
UOUT V
Variable
Load,
0-40A
Voltage Drop = U1 - UOUT
Fig. 3-2 Input to output voltage drop when only one input draws current
Voltage Drop, typ.
160mV
140mV
120mV
100mV
A... 25°C
B... 60°C
BA
80mV
60mV
40mV
20mV
0mV
Output Current
0
5A 10A 15A 20A
QS/QT20
24V,20A
+
-
I1
A
V U1
YR40
Input 1
Not used or
power supply
with lower
voltage
Input 2
Output
Output
IOUT
A
UOUT V
Variable
Load,
0-20A
Voltage Drop = U1 - UOUT
Feb. 2014 / Rev. 1.3 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
4/17