17.6. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Curve A2
Recommended output current.
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 17-3
Mounting
Orientation A
(Standard
orientation)
INPUT
YR40
Redundancy
Module
OUTPUT
Output Current
40A
A1
30
20
10
0
20
Ambient Temperature
30 40 50 60
70°C
Fig. 17-4
Mounting
Orientation B
(Upside down)
Output Current
40A
A1
30
20
10
0
20
Ambient Temperature
30 40 50 60
70°C
Fig. 17-5
Mounting
Orientation C
(Table-top
mounting)
Output Current
40A
30
A2
20
A1
10
0
20
Ambient Temperature
30 40 50 60
70°C
Fig. 17-6
Mounting
Orientation D
(Horizontal cw)
Output Current
40A
30
A2
20
A1
10
0
20
Ambient Temperature
30 40 50 60
70°C
Fig. 17-7
Mounting
Orientation E
(Horizontal ccw)
Output Current
40A
30
A2
20
A1
10
0
20
Ambient Temperature
30 40 50 60
70°C
Feb. 2014 / Rev. 1.3 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany