YRM2.DIODE Datasheet, PDF (5/19 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YRM2.DIODE
DC24-48V, 20A, DUAL REDUNDANCY MODULE
4. POWER LOSSES
Power losses
typ.
typ.
typ.
Standby power losses
typ.
DC 24V
8.8W
9.5W
18.0W
1.0W
Fig. 4-1 Power losses
Power Losses, typ.
24W
20
16
12
8
4
Output Current
0
0
5
10 15 20
25A
input: 2x5A
input: 1x10A
input: 2x10A
at no output current
5. ALARM CONTACTS
Both input voltages are monitored individually. If one input voltage is too low or completely lost, it will be indicated
by an alarm relay contact.
Each input has its own monitoring circuitry and relay contact.
Alarm threshold
Contact ratings
Isolation voltage
nom.
21.5V (±0.5V)
min. 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A
max.
1mA at 5Vdc
see dielectric strength table in section 14.
Relay contact opens immediately after
the input voltage falls below this value.
input: 1x10A
input: 2x10A
Apr. 2014 / Rev. 1.4 DS-YRM2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany