English
Language : 

YRM2.DIODE Datasheet, PDF (16/19 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YRM2.DIODE
DC24-48V, 20A, DUAL REDUNDANCY MODULE
18.4. EXAMPLE: N+1 REDUNDANCY UP TO 30A
N+1 Redundancy up to 30A requires four 10A power supplies and two YRM2.DIODE redundancy modules.
Fig. 18-2 Wiring diagram, n+1 Redundancy, 30A output current
Failure
Monitor
+ +--
24V, 10A
+ -+ -
IN 1 IN 2 IN 1 IN 2
+ +--
24V, 10A
+ +--
24V, 10A
+ -+ -
IN 1 IN 2 IN 1 IN 2
+ +--
24V, 10A
10A
Power Supply
YRM2.DIODE
10A
Power Supply
10A
Power Supply
YRM2.DIODE
10A
Power Supply
L N PE
I
L
N
PE
+OU-T
optional
L N PE
I
L N PE
I
+OU-T
optional
Note: Use separate mains systems for each power supply whenever it is possible
L N PE
I
30A
Load
18.5. EXAMPLE: BATTERY BACK-UP
A battery back-up with 10A requires one 10A power supply and one YRM2.DIODE redundancy module.
Please note:
Set output voltage of power supply to 26.5Vdc minimum to ensure, that the load current is delivered from the power
supply and not from charger (battery). Use a fuse between battery and YRM2.DIODE!
Fig. 18-3 Wiring diagram, 10A Battery back-up
I
24V Battery
-
Battery
Charger
L
N
PE
Failure
Monitor
+ +--
24V, 10A
+ -+ -
IN 1 IN 2 IN 1 IN 2
10A
Power Supply
YRM2.DIODE
L N PE
+OU-T
optional
10A
Load
Apr. 2014 / Rev. 1.4 DS-YRM2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
16/19