YR40.245 Datasheet, PDF (2/18 Pages) PULS GmbH – SINGLE REDUNDANCY MODULE
Y-Series
YR40.245
12-28V, 40A, SINGLE REDUNDANCY MODULE
INDEX
Page
1. Intended Use .......................................................3
2. Installation Requirements...................................3
3. Input and Output Characteristics .......................4
4. Power Losses........................................................5
5. Lifetime Expectancy and MTBF...........................6
6. Terminals and Wiring..........................................7
7. Replacing Units while the System is Running ....8
8. Functional Diagram.............................................9
9. Front Side and User Elements.............................9
10. EMC....................................................................10
11. Environment ......................................................11
12. Protection Features ...........................................12
13. Safety Features ..................................................12
Page
14. Dielectric Strength............................................ 12
15. Approvals .......................................................... 13
16. Physical Dimensions and Weight ..................... 14
17. Accessories ........................................................ 15
18. Application Notes............................................. 16
18.1. Recommendations for Redundancy.........16
18.2. Inductive and Capacitive Loads................16
18.3. Sidewards Installation Clearances............16
18.4. 1+1 Redundancy up to 40A......................17
18.5. N+1 Redundancy, Example with 120A ....17
18.6. Mounting Orientations ............................18
The information presented in this document is believed to be accurate and reliable and may change without notice.
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
TERMINOLOGY AND ABREVIATIONS
PE and symbol
Earth, Ground
T.b.d.
DC 24V
24Vdc
may
shall
should
1+1 Redundancy
N+1 Redundancy
PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
This document uses the term “earth” which is the same as the U.S. term “ground”.
To be defined, value or description will follow later.
A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
A figure with the unit (Vdc) at the end is a momentary figure without any additional
tolerances included.
A key word indicating flexibility of choice with no implied preference
A key word indicating a mandatory requirement
A key word indicating flexibility of choice with a strongly preferred implementation
Use of two identical power supplies in parallel to provide continued operation following most
failures in a single power supply. The two power supply outputs should be isolated from each
other by utilizing diodes or other switching arrangements. E.g. two 10A power supplies are
needed to achieve a 10A redundant
system.
Use of three or more identical power
supplies in parallel to provide
continued operation following most
N+1
Redundancy
AC
AC
AC
AC
DC
DC
DC
DC
1+1
Redundancy
AC
AC
DC
DC
failures in a single power supply. All
power supply outputs should be
IN
IN
IN
IN
IN
IN
isolated from each other by utilizing
diodes or other switching
OUT
OUT
OUT
OUT
OUT
OUT
arrangements.
E.g.: To achieve a 30A redundant
-
-
system, four 10A power supplies are
Load
Load
needed in a N+1 redundant system.
Apr. 2014 / Rev. 1.1 DS-YR40.245-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
2/18