English
Language : 

YR40.245 Datasheet, PDF (10/18 Pages) PULS GmbH – SINGLE REDUNDANCY MODULE
Y-Series
YR40.245
12-28V, 40A, SINGLE REDUNDANCY MODULE
10. EMC
The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions. A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
20V/m
Criterion A
Fast transients (Burst)
Surge voltage on input
lines
Surge voltage on output
lines
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
Input lines
Output lines
+Æ-
+/- Æ Chassis ground
+Æ-
+/- Æ Chassis ground
2kV
2kV
500V
1kV
500V
1kV
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
20V
Criterion A
Power-frequency magnetic EN 61000-4-8
field *)
50Hz
30A/m
Criterion A
Criterions:
A: Redundancy module shows normal operation behavior within the defined limits.
Notes:
*) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power ports according
EN 61000-6-3 fulfilled *)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) For information only, not mandatory for EN 61000-6-3. Provided, that power sources connected on the inputs fulfill the requirements too.
Switching frequency
The internal auxiliary supply is generated with a boost converter.
The switching frequency varies from 140kHz to 500kHz depending on the input voltage.
Apr. 2014 / Rev. 1.1 DS-YR40.245-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
10/18