English
Language : 

CAT25128LI-G Datasheet, PDF (9/20 Pages) ON Semiconductor – 128-Kb SPI Serial CMOS EEPROM
CAT25128
Byte Write
Once the WEL bit is set, the user may execute a write
sequence, by sending a WRITE instruction, a 16−bit address
and data as shown in Figure 5. Only 14 significant address
bits are used by the CAT25128. The rest are don’t care bits,
as shown in Table 14. Internal programming will start after
the low to high CS transition. During an internal write cycle,
all commands, except for RDSR (Read Status Register) will
be ignored. The RDY bit will indicate if the internal write
cycle is in progress (RDY high), or the device is ready to
accept commands (RDY low).
Page Write
After sending the first data byte to the CAT25128, the host
may continue sending data, up to a total of 64 bytes,
according to timing shown in Figure 6. After each data byte,
the lower order address bits are automatically incremented,
while the higher order address bits (page address) remain
unchanged. If during this process the end of page is
exceeded, then loading will “roll over” to the first byte in the
page, thus possibly overwriting previously loaded data.
Table 14. BYTE ADDRESS
Main Memory Array
Identification Page*
*New Product only.
Address Significant Bits
A13 − A0
A5 − A0
Following completion of the write cycle, the CAT25128 is
automatically returned to the write disable state.
Write Identification Page
The additional 64−byte Identification Page (IP) can be
written with user data using the same Write commands
sequence as used for Page Write to the main memory array
(Figure 6). The IPL bit from the Status Register must be set
(IPL = 1) using the WRSR instruction, before attempting
to write to the IP.
The address bits [A15:A6] are Don’t Care and the
[A5:A0] bits define the byte address within the
Identification Page. In addition, the Byte Address must point
to a location outside the protected area defined by the BP1,
BP0 bits from the Status Register. When the full memory
array is write protected (BP1, BP0 = 1,1), the write
instruction to the IP is not accepted and not executed.
Also, the write to the IP is not accepted if the LIP bit from
the Status Register is set to 1 (the page is locked in
Read−only mode).
Address Don’t Care Bits
A15 − A14
A15 − A6
# Address Clock Pulses
16
16
CS
SCK
SI
012345678
21 22 23 24 25 26 27 28 29 30 31
00
OPCODE
00 0 01
BYTE ADDRESS*
DATA IN
0 AN
A0 D7 D6 D5 D4 D3 D2 D1 D0
SO
HIGH IMPEDANCE
Dashed Line = mode (1, 1)
* Please check the Byte Address Table (Table 14)
Figure 5. Byte WRITE Timing
CS
SCK
012345678
21 22 23 24−31 32−39 24+(N−1)x8−1 .. 24+(N−1)x8
24+Nx8−1
OPCODE
BYTE ADDRESS*
DATA IN
Data Byte N
SI
0 0 0 0 0 0 1 0 AN
A0
7..1 0
Data Data Data
Byte 1 Byte 2 Byte 3
HIGH IMPEDANCE
SO
Dashed Line = mode (1, 1)
* Please check the Byte Address Table (Table 14)
Figure 6. Page WRITE Timing
http://onsemi.com
9