H3DK Datasheet, PDF (22/30 Pages) Omron Electronics LLC – Solid-state Timers
H3DK-H
*1. DC ripple: 20% max. (A single-phase, full-wave rectifying power supply can be connected.)
*2. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*3. The control output ratings are for one H3DK operating alone.
If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity (Reference Values) on the next page.
■ Characteristics
Accuracy of operating
time
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
Setting error
±10% of FS ±0.05 s max.
Influence of voltage
±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of tempera-
ture
±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength
Between current-carrying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1 min.
Impulse withstand volt-
age
Between power supply terminals: 1 kV for 24-VAC/DC and 48-VAC/DC models,
3 kV for all other models.
Between current-carrying metal parts and exposed non-current-carrying metal
parts): 1.5 kV for 24-VAC/DC and 48-VAC/DC models, 4.5 kV for all other
models.
Noise immunity
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV (between power supply terminals)
Static immunity
Malfunction: 4 kV, Destruction: 8 kV
Vibration Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
resistance Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
● Installation Pitch and Output
Switching Capacity (Reference
Values)
The relation between the installation pitch
and the load current is shown in the fol-
lowing graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the tempera-
ture inside the Timer will increase, reduc-
ing the life expectancy of internal parts.
80
70
60
d = 50 mm
50
d = 10 mm
d = 5 mm
40
30
d = 0 mm
20
Shock re- Destruction 1,000 m/s2 3 times each in 6 directions
10
sistance Malfunction 100 m/s2 3 times each in 6 directions
Life ex- Mechanical 10 million operations min. (under no load at 1,200 operations/h)
pectancy Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
0
1
2
3
4
5
6
Load current (A)
Degree of protection
Weight
IP30 (Terminal block: IP20)
Approx. 120 g
■ Applicable standards
Safety standards
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
Testing Method
Tested Timer: H3DK-H
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
1
Test
timer
2
Test
timer
3
Test
timer
4
Test
timer
5
DIN Track Timer installation pitch: d
EMC
(EMI)EN61812-1
Radiated Emissions:EN 55011 class B
Emission AC Mains:EN 55011 class B
Harmonic Current:EN 61000-3-2
Voltage Fluctuations and Flicker:EN61000-3-3
(EMS)EN61812-1
ESD Immunity:EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity:EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:EN 61000-4-5: 2 kV common mode,
1 kV differential mode
■ I/O
Input
Output
Control output
None
The Timer operates as soon as the Timer is turned ON. The
Timer starts timing when the power is turned OFF and the output
is turned OFF when the time set on the dial elapses.
22