English
Language : 

H3DK Datasheet, PDF (14/30 Pages) Omron Electronics LLC – Solid-state Timers
H3DK-F
Dimensions
■ Timers
H3DK-F
(Unit: mm)
22.5
79 65.6 52
100
88.2
69.1
4
89.4
■ Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
■ Basic Operation
Setting the Time Ranges
● Setting the Time Ranges
Use the ON time range switch to set the
ON time range and the OFF time range
switch to set the OFF time range. Turn
the switches with a flat-blade or Phillips
screwdriver.
Setting the ON/OFF Start Switch
● Setting an ON Start or OFF Start
The ON/OFF start switch can be used to
switch between ON-start and OFF-start
operation.
Setting the Times
● Setting the Times
Use the ON time setting dial and the
OFF time setting dial to set the ON time
and OFF time.
ON time range
switch
OFF time range
switch
ON/OFF start
switch
ON time setting dial
OFF time setting dial
■ Timing Charts
Flicker OFF start
Flicker ON start
Power (A1 and A2) ON
OFF
ON indicator (15 and 18) ON
OFF
tON
tON
tOFF
tOFF
tOFF
OFF indicator (15 and 16) ON
OFF
Output (15 and 18) ON
OFF
tON: ON set time
tOFF: OFF set time
0.1 s min.
tOFF
Power (A1 and A2) ON
OFF
ON indicator (15 and 18) ON
OFF
tON
tON
tON
tOFF
tOFF
OFF indicator (15 and 16) ON
OFF
Output (15 and 18) ON
OFF
tON: ON set time
tOFF: OFF set time
0.1 s min.
tON
Note 1. The reset time is 0.1 s min.
Note 2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance of the Timer.
14