H3DK Datasheet, PDF (20/30 Pages) Omron Electronics LLC – Solid-state Timers
H3DK-G
Operating Procedures
■ Basic Operation
Setting the Time Ranges
● Setting the Delta Time Range and the Star-delta Transfer
Time (t2)
Star Time (t1) Range
Set the star-delta transfer time.
For ×1 (1 to 12 s), use side (A) (labeled “t1×1”).
For ×10 (10 to 120 s), use side (B) (labeled “t10×1”).
(See following diagram.)
Star-delta transfer
time setting (t2)
Switches the start
time (t1) range.
(A)
0.5s
0.25s
0.1s
0.05s
t2
t1x1
(B)
0.5s
0.25s
0.1s
0.05s
t2
t1x10
■ Timing Chart
ON
Power (A1 and A2) OFF
Star contacts (15 and 18) ON
OFF
t1
t2
ON
Delta contacts (25 and 26) OFF
Star operation indicator
ON
OFF
Delta operation indicator
ON
OFF
t1: Star time setting
t2: Transfer time
Note: “t1” is the start set time. “t2” is the transfer time.
Setting the Time
● Setting the Time
The start time is set with the main dial.
Main dial
0.5 s min.