S8AS Datasheet, PDF (20/26 Pages) Omron Electronics LLC – Smart Power Supply | |||
|
◁ |
S8AS
Alarm Display
The S8AS displays alarms according to the parameters set in Setting
Mode. The alarm number and detected value are alternated on the
display for each alarm.
Example: Abnormal Current Tripping Alarm at Branch Output 4
0.5 s
1 2 3 4 5 6 V A Yrs °C s
0.5 s
1 2 3 4 5 6 V A Yrs °C s
0.5 s
0.5 s
Current when
alarm occurred
Note: Indicator Status Notation
Lit
Flashing
1 2 3 4 5 6 V A Yrs °C s
Note: Alarms will be displayed in order of priority if more than one
alarm occurs at the same time.
Order of priority: A10, A12, A11, A23/HOT, A21, A23, A30.
Resetting Alarms
When an alarm is displayed, remove the cause of the alarm and then
press the Reset Key ( ) for at least 3 s.
The following display will appear and the alarm will be reset.
For information on resetting alarms, refer to List of Alarms on the
previous page.
Communications (S8AS-24006R/48008R)
The built-in RS-485 port can be used to connect special Support Tool
to set parameters, monitor, perform tripping operations for branch
outputs, and perform other remote monitoring and control operations
from a network.
Type
Communications
method
Sync method
Baud rate
Transmitted code
Data bit length
Stop bit length
Error detection
Parity check
Protocol
RS-485
Half-duplex
Start-stop
4,800 or 9,600 bps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity and BCC
None, even, or odd
CompoWay/F
Support Tool (S8AS-24006R/48008R)
The Support Tool is used to set and monitor models that support
communications. Parameters can be set, operation can be monitored,
and parameter files can be managed.
Support Tool Functions
⢠Reading and writing parameter settings
⢠Monitoring present values
⢠Monitoring status (cutoff status, normal/error status)
Applicable OS: Windows 2000 or XP
Visit OMRON's website for downloading the Support Tool.
20
|
▷ |