Chart 5: Operation Timing
Power supply voltage
Branch output 1 voltage
Branch output 2 voltage
Branch output 3 voltage
Startup sequence time
Startup sequence time
Startup sequence time
Branch output 6 or
branch output 8 voltage
Startup sequence time
Self-diagnostics
(0.5 s min.)
Note: For the S8AS-24006N and S8AS-48008N, the settings are
0.0 s for branch output 1, 0.4 s for branch output 2, 0.8 s for
branch output 3, 1.2 s for branch output 4, 1.6 s for branch
output 5, 2.0 for branch output 6, 2.4 s for branch output 7, and
2.8 s for branch output 8. (Cannot be changed.)
(Branch outputs 7 and 8 are available only with the S8AS-
48008N.)
Chart 6: Operation Timing
External tripping input
Branch output 1 voltage
Branch output 2 voltage
Branch output 3 voltage
Shutdown sequence time
Shutdown sequence time
Shutdown sequence time
Branch output 6 or
branch output 8 voltage
Shutdown sequence time
20 ms max.
Note: 1. Cut off simultaneously for tripping for abnormal voltages
(28.8 V or higher).
2. For the S8AS-24006N and S8AS-48008N, all branch
outputs have a setting of 0.0 s. (Cannot be changed.)