English
Language : 

F10-1D22-BKK Datasheet, PDF (19/28 Pages) Magnetrol International, Inc. – Flow Switches
4.4.3 Model F10 Dimensional Specifications
Inches (mm)
10.12
(257)
A
2.50
(63) B 1.56 (40)
5.93 (150)
3.87 (98)
FLOW
NOTE: For proper performance, a straight pipe run of 12 pipe diameters upstream
and 3 pipe diameters downstream of the switch is recommended.
8.46
(214)
A
plugged
2" NPT 3000# Bonney Threadolet
or Equal (Supplied by Customer)
Line
Size
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
8"
Over
8"
Dim. B
Max.
Equivalent
Max. Wall
Schedule
1.81 (46)
80
1.94 (49) 160
1.88 (48)
80
1.88 (48)
80
2.00 (51) 120
2.06 (52) 120
2.12 (54) 120
2.19 (56) 100
2.31 (59)
—
Vane length dependent
upon line size
Pipe Line Size
(Horizontal Lines Only)
2.56 (62) Dia. .06 (2)
1.75
Vane
(44)
Width
1.50
(38)
F10 with 2" NPT Connection
3" Pipe and Up
2" and 2 1/2" Pipe
5.93 (150)
3.87 (98)
CONDUIT CONNECTIONS A
Electrical Switches:
NEMA 4X/7/9: 1" NPT
Group B:
1" NPT
Pneumatic Switches:
NEMA 1:
1/4" NPT
All housings rotatable 360°
Notes:
1. Allow the following for overhead
clearance for cover removal:
NEMA 1 —
8.00 (203)
NEMA 4X/7/9 — 10.00 (254)
Group B —
10.00 (254)
10.12
(257)
A
5.25
(133)
7.38
(187)
Top of
pipe run
Flow Vane
8.46
(214)
A plugged
2 1/2" ANSI
Mounting Flange
2 1/2" ANSI Flange
(to match F10)
Standoffs (Qty. 3)
3.00 (76) Diameter
0.19 (5) Minimum
F10 with Flanged Connection
47-602 F10 and F50 Flow Switches
19