F10-1D22-BKK Datasheet, PDF (14/28 Pages) Magnetrol International, Inc. – Flow Switches
4.2 Agency Approvals
AGENCY
MODEL
FM
F10-XXXX-XXX
F50-XXXX-XXX
F10-XXXX-XXX
F50-XXXX-XXX
CSA
F10-XXXX-XXX
F50-XXXX-XXX
F10-XXXX-XXX
F50-XXXX-XXX
F10-XXXX-XXX
F50-XXXX-XXX
ATEX/IEC Ex ΠF10-XXXX-XXX
F50-XXXX-XXX
CE
F10-XXXX-XXX
F50-XXXX-XXX
APPROVAL
with an electric switch mechanism and a housing
listed as Type 4X/7/9
with an electric switch mechanism and a housing
listed as Type 4X/7/9 Class I, Div 1, Group B
with a Series F or HS electric switch
mechanism and a housing listed as CSA Type 4X
with an electric switch mechanism and a housing
listed as Type 4X/7/9
with an electric switch mechanism and a housing
listed as Type 4X/7/9 Class I, Div 1, Group B
with an electric switch mechanism and an
ATEX housing
Low Voltage Directives 2006/95/EC
Per Harmonized Standard:
EN 61010-1/1993 & Amendment No. 1
CATEGORIES
Class I, Div 1, Groups C & D
Class II, Div 1, Groups E, F & G
Class I, Div 1, B, C & D
Class II, Div 1, Groups E, F & G
Class I, Div 2, Group B
Class I, Div 1, Groups C & D
Class II, Div 1, Groups E, F & G
Class I, Div 1, Groups B, C & D
Class II, Div 1, Groups E, F & G
ATEX II 2 G EEx d IIC T6
94/9/EC
IEC Ex Ex d IIC T6
IP66
Installation Category II
Pollution Degree 2
ΠIEC Installation Instructions:
The cable entry and closing devices shall be Ex d certified suitable for the conditions of use
and correctly installed.
For ambient temperatures above +55° C or for process temperatures above +150° C, suitable
heat resistant cables shall be used.
Heat extensions (between process connection and housing) shall never be insulated.
Special conditions for safe use:
When the equipment is installed in process temperatures higher than +85° C the temperature
classification must be reduced according to the following table as per IEC60079-0.
Maximum Process
Temperature
< 85° C
< 100° C
< 135° C
< 200° C
< 300° C
< 450° C
Temperature
Classification
T6
T5
T4
T3
T2
T1
These units are in conformity with IECEx KEM 05.0020X
Classification Ex d IIC T6
Tambient -40° C to +70° C
14
47-602 F10 and F50 Flow Switches