805-501A-111 Datasheet, PDF (16/36 Pages) Magnetrol International, Inc. – KOTRON® MODEL 805 SMART RF LEVEL TRANSMITTER
Display
*Level*
1
*%Output*
*Loop*
2
Level
xx.x lu
3
%Output
xx.x%
4
Loop
xx.xx mA
5
Units
lu
6
Lo Cal
xxx.x lu
7
Lo Cap
xxxx pF
8
Hi Cal
xxx.x lu
9
Hi Cap
xxxx pF
10
Set 4mA
xxx.x lu
11
Set 20mA
xxx.x lu
12
Damping
xx sec
13
Fault
Choice
14
Poll Adr
xx
15
Trim 4
xxx
16
Trim 20
xxxx
17
Loop Tst
xx.x mA
18
Prb Rdg
xxxx pF
19
Osc Tst
xxxx tk
20
Opn Prb
xxxx tk
21
# Ticks
xxxxx tk
22
Reinit
xx
23 Ver n.nAa
24
New Pass
xxx
Action
Comment
Transmitter Display
Transmitter Display
Transmitter default display. Level, % Output, and Loop
values cycle every 5 seconds (two seconds each value).
Level measurement in cm or in.
Transmitter Display
Level as percentage of loop current (20 mA) span.
Transmitter Display
Select units for level
measurement display.
Enter level value for the
lower calibration point.
Transmitter Display
Loop current output.
lu = cm or in.
Use Up and Down keys to set reading to present level of
medium in vessel. See Section 1.4.
Measured capacitance at low calibration point.
Enter level value for the
higher calibration point.
Transmitter Display
Move the level in the tank. Use Up and Down keys to set
reading to present level of medium in vessel. See Section 1.4.
Measured capacitance at high calibration point.
Enter the level value for the
4 mA point.
Enter the level value for the
20 mA point.
Enter damping factor.
Enter the desired loop current
in presence of a fault.
Enter HART poll address.
Trim loop current to 4.00 mA.
Trim loop current to 20.00 mA.
Use Up and Down keys to set reading to level corresponding
to 4 mA loop current.
Use Up and Down keys to set reading to level corresponding
to 20 mA loop current.
Choose the damping factor (1–45 sec) for smoothing the
level/output/loop displays.
Select 22 mA, 3.6 mA or Hold. (3.6 mA is not valid if unit
includes both digital display and HART)
Select a HART poll address (0–15). Enter 0 for a single
transmitter installation.
With a meter in the loop, use Up and Down keys to adjust
current to 4.00 mA.
With a meter in the loop, use Up and Down keys to adjust
current to 20.00 mA.
Enter test value of loop current
Transmitter Display
Use Up and Down keys to set loop current to a desired value
(3.5–22.0 mA) for testing.
Measured capacitance at present level of medium in vessel.
Transmitter Display
Transmitter Display
Transmitter Display
Select Yes to reinitialize
all values
Transmitter Display
Internal timing count with known capacitance in circuit
(factory diagnostic).
Internal timing count with probe disconnected (factory
diagnostic).
Internal timing count at present level of medium in vessel
(factory diagnostic).
Resets all configuration parameters to factory default
values.
Shows version number of firmware.
Enter new password
Use Up and Down keys to select desired value (0–255).
13
50-660 Kotron Model 805 Smart RF Level Transmitter