FGF506D Datasheet, PDF (4/4 Pages) Gamewell-FCI by Honeywell – Pre-action / Deluge Control Panel
System Specifications
System Capacity:
Annunciators ............8
Electrical Specifications
Flex GF506D
(FLPS-7 Power Supply): 120 VAC, 50/60 Hz, 2.3 amps
Wire size:
minimum 14 AWG (2.0 mm²)
with 600 V insulation,
supervised, non power-limited
Cabinet Specifications
Door
Dimensions:
19.26" H x 16.82" W x 0.72"
(48.92 H x 42.73 W x 1.82 D cm)
Backbox:
19.00" H x 16.65" W x 5.25" D
Dimensions:
(48.26 H x 42.29 W x 13.34 D cm)
Trim Ring (TR- CE):
Dimensions:
22.00" high x 19.65" wide
(55.88 H x 49.91 W cm)
Shipping Specifications
Dimensions:
- Height 20.00" (50.80cm)
- Width 22.50" (57.15cm)
- Depth 8.50" (21.59cm)
System Specifications (Continued)
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0°
–49°C/32° – 120°F and at a relative humidity 93% ± 2%
RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). How-
ever, the useful life of the system's standby batteries and
the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is
recommended that this system and its peripherals be
installed in an environment with a normal room tempera-
ture of 15° – 27°C/60° – 80°F.
NFPA Standards
The GF506D complies with the following NFPA 72 Fire
Alarm Systems requirements:
- NFPA 13 Installation of Sprinkler Systems
- NFPA 15 Water Spray Fixed Systems
- NFPA 16 Deluge Foam-Water Sprinkler and Foam-
Water Spray Systems
- NFPA 72 National Fire Alarm Code for Local Fire
Alarm Systems and Remote Station Fire Alarm
Systems (requires an optional Remote Station Output
Module)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60466 Rev. D page 4 of 4
www.gamewell-fci.com