FGF506D Datasheet, PDF (2/4 Pages) Gamewell-FCI by Honeywell – Pre-action / Deluge Control Panel
Features (Continued)
• History Log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt DC operation.
• Low AC voltage sense.
• Outputs Programmable for the following:
- Releasing circuits or NACs
• NACs programmable for the following:
- Silence Inhibit
- Auto-Silence
- Strobe Synchronization
- Selective Silence (horn-strobe mute)
- Temporal or Steady Signal
- Silenceable or Non-silenceable
- Release Stage Sounder
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Automatic battery charger with charger supervision.
• Optional Dress Panel DP-51050 (red).
• Optional Trim Ring TR-CE (red) for semi-flush
mounting the cabinet.
• Optional CAC-5X Class A Converter Module for
Outputs and IDCs.
• Optional 4XTMF Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD,
411UDAC).
Programming and Software
The programming software offers the following features:
• Custom English labels (per point) may be manually
entered or selected from an internal library file.
• Three programmable Form-C relay outputs.
• Pre-programmed and custom application templates.
• Continuous fire protection during online programming
at the front panel.
• Program Check automatically catches common errors
not linked to any zone or input point.
User Interface
The user interface features are listed below:
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight
savings adjustments.
• ANN-Bus for connection to remote annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
The panel provides the following LED Indicators:
• Fire Alarm (red)
• AC Power (green)
• Supervisory (yellow) • Alarm Silenced (yellow)
• Trouble (yellow)
• Discharge (red)
Control Buttons
• Acknowledge
• Alarm Silence
• System Reset (lamp test)
• Drill
Features (Continued)
AC Power – TB1
The AC Power -TB1 for each panel is listed below:
• GF506D:
120 VAC, 50/60 Hz, 2.3 amps
• Wire size: minimum #14 AWG (2.0 mm2) with 600V
insulation.
• Supervised, non power-limited
Battery (sealed lead acid only) – J12:
The Battery (for sealed lead acid only) - J12 specifications
are listed below.
• Maximum Charging Circuit - Normal Flat Charge:
- 27.6 VDC @ 1.4 amp. Supervised, non power-limited.
• Maximum Charger Capacity:
- 26 Amp Hour battery (two 18 Amp Hour batteries can
be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or
BB-55).
• Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 and TB6
The Initiating Device Circuits for TB4 and TB6
specifications are listed below.
• Alarm Zones 1 - 5 on TB4
• Alarm Zone 6 on TB6
• Supervised and power-limited circuitry
• Style B (Class B) wiring with Style D (Class A) option
• Normal Operating
Voltage:
Nominal 20 VDC
• Alarm Current:
15 mA minimum
• Short Circuit Current: 40 mA max
• Maximum Loop
Resistance:
100 Ohms
• End-of-Line Resistor: 4.7KOhms, 1/2 watt
(PN 71252)
• Standby Current:
4 mA
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
Notification Appliance and Releasing Circuit(s) -
TB5 and TB7
The notification appliance and releasing circuits for TB5
and TB7 specifications are listed below.
• Four Output Circuits.
• Style Y (Class B) or Style Z (Class A) with optional
converter module
• Strobe synchronization
• Special Application power
• Supervised and power-limited circuitry
• Normal Operating
Voltage:
Nominal 24 VDC
• Maximum Signaling
Current:
7.0 amps (3.0 amps
maximum per NAC)
• End-of-Line Resistor: 4.7KOhms, 1/2 watt
(PN71252)
• Max. Wiring Voltage
Drop:
2 VDC
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.