English
Language : 

FGF506D Datasheet, PDF (1/4 Pages) Gamewell-FCI by Honeywell – Pre-action / Deluge Control Panel
Flex GF506D
Description
General
The Flex GF506D is a six-zone FACP used for single and
dual hazard deluge and pre-action applications. The Flex
GF506D provides reliable fire detection. It also offers sig-
naling and protection for commercial, industrial, and insti-
tutional buildings that require water-based releasing. The
Flex GF506D is compatible with System Sensor’s i3 detec-
tors.
The i3 detectors are conventional smoke detectors that
transmit a maintenance trouble signal to the FACP that
indicates the need for cleaning. It also transmits a supervi-
sory ‘freeze’ signal when the ambient temperature falls
below the detector rating of approximately 45°F (7.22°C).
In addition, the Flex GF506D control panel is compatible
with the following conventional input devices:
• two-wire and four-wire smoke detectors
• pull stations
• waterflow devices and tamper switches
• other normally-open contact devices
For a complete listing of compatible devices, refer to the
Gamewell-FCI Device Compatibility Document,
P/N: 52195.
There are four outputs that are programmable as NACs
(Notification Appliance Circuits) or releasing circuits. Three
programmable Form-C relays (factory programmed for
Alarm, Trouble, and Supervisory), and the 24 VDC special
application resettable and non-resettable power outputs
are included on the main circuit board. The Flex GF506D
supervises all wiring, AC voltage, battery charger, and
battery level.
The activation of a compatible smoke detector or any nor-
mally open fire alarm initiating device will do the following:
• turn on audible and visual signaling devices
• light an indicator
• display alarm information on the panel’s LCD
• sound the piezo sounder at the FACP
• activate the FACP alarm relay
• operate an optional module used to notify a remote
station or initiate an auxiliary control function
Pre-action / Deluge Control Panel
Features
Flex GF506D
• Listed to UL Standard 864, 9th Edition.
• IBC Seismic Certified.
• Designed for sprinkler standards NFPA 13, 15 and 16.
• Dual hazard operation.
• Adjustable waterflow discharge timer and two soak timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating
Device Circuit) with optional Class A wiring.
• System Sensor i3 series detectors compatible.
• Four programmable Style Y (Class B) output circuits -
(special application power) with Class A Style Z option.
• Strobe Synchronization:
- System Sensor - Cooper-Wheelock -Gentex
- Faraday
- Amseco
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
• ANN-BUS for connection to optional
(up to 8 total of any of the following):
-GFANN-80 Remote LCD Annunciator
-GFANN-RLY Relay Module
-GFANN-LED Annunciator Module
• 80-character LCD display (backlit).
• Real-time clock/calendar w/daylight savings time control.
i 3™ is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriter’s Laboratories Inc.
SIGNALING
S624
FM
Reference Certificate
APPROVED
of Compliance
7165-1703:0171 VMA-45894-02C
(Revision 1)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60466 Rev. D page 1 of 4