FGF506D Datasheet, PDF (3/4 Pages) Gamewell-FCI by Honeywell – Pre-action / Deluge Control Panel
Features (Continued)
Form-C Relays - Programmable - TB8
The Form-C Relays for TB8 specifications are listed below.
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe
Trouble Relay)
• Relay 3 (factory default programmed as Supervisory
Relay).
• Relay Contact Ratings:
- 2 amps @ 30 VDC (resistive)
- 2 amps @ 30 VAC (resistive)
Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit
which can be used to monitor external devices for trouble
conditions. It can be connected to the trouble bus of a
peripheral, such as a power supply, which is compatible
with open collector circuits.
Special Application Resettable Power - TB9
The Special Application Resettable Power - TB9
specifications are listed below.
• Operating Voltage:
Nominal 24 VDC
• Maximum Available
Current:
500 mA - appropriate for
powering 4-wire smoke
detectors (see note 1).
• Power-limited Circuitry
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
NOTE 1: Total current for resettable power, non-resettable
power and Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Non-resettable
Power - TB9
The Special Application Resettable or Non-resettable
Power - TB9 specifications are listed below.
• Operating Voltage:
Nominal 24 VDC
• Maximum Available
Current:
500 mA (see Note 1)
• Power-limited circuitry
• Jumper selectable by JP31 for resettable or non-reset-
table power.
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
Product Line Information
Product
GF506D
CAC-5X
4XTMF
GFANN-80
GFANN-LED
GFANN-RLY
DP-51050
TR-CE
BB-17F
PRN-6
PRT/PK-Cable
Description
Six-zone, 24 volt Pre-action Deluge Con-
trol Panel (includes backbox, power sup-
ply, technical manual, and a frame &
post operating instruction sheet) for sin-
gle and dual hazard deluge and pre-
action applications.
Class A Converter Module can be used
to convert the Style B (Class B) Initiating
Device Circuits to Style D (Class A) and
Style Y (Class B) Output Circuits to Style
Z (Class A).
Transmitter Module provides a super-
vised output for the local energy munici-
pal box transmitter and the alarm and
trouble reverse polarity. It includes a dis-
able switch and disable trouble LED.
LCD Annunciator is a remote LCD
annunciator that mimics the information
displayed on the FACP LCD display. The
recommended wire type is unshielded.
Annunciator Module provides three
LEDs for each zone: Alarm, Trouble and
Supervisory. Ships with enclosure (red
and black enclosures available; refer to
P/N: DF-60241).
Relay Module, which can be mounted
inside or outside the cabinet, provides 10
programmable Form-C relays.
Dress panel (red) is available as an
option. The dress panel restricts access
to the system wiring while allowing
access to the membrane switch panel.
Trim-ring (red) is available as an option.
The trim-ring allows semi-flushing
mounting of the cabinet.
Battery box, holds up to two (2) 18 Amp
Hour batteries.
Battery box, houses two (2) 55 Amp
Hour batteries, red.
Refer to P/N: DF-52397.
UL-Listed compatible event printer. Dot-
matrix, tractor-fed paper, 120 VAC.
Programming cable.
Use this cable to update the FACPs
Flash firmware. (Also it requires an
RS485 to RS232 converter).