English
Language : 

60132 Datasheet, PDF (8/9 Pages) List of Unclassifed Manufacturers – 60132 Circuit Breaker
Multi 9Â¥ System Catalog
Section 2—UL and CSA Rated Protection Devices
UL 489 Listed C60 Circuit Breakers (DC)
Overview
A portion of the range of UL 489 circuit breakers are also Listed by UL for use with dc circuits. The
specifications are the same as the UL 489 circuit breakers, with the following exceptions:
• Number of poles: 1 and 2
• Time/current curve: C curve
• Magnetic setting of C curve: between 7 and 14 times ampere rating
• DC voltage (nominal): 1 pole—60 Vdc, 2 pole—125 Vdc
• Connection: box lug only (same torque)
Table 9: Specifications for UL 489 C60 DC Circuit Breakers
Ratings per UL Standards
Number of Poles
Rated Current (A) at 77°F (25°C)
Interrupting Ratings per UL 489 (kA)
Service Breaking Capacity (Ics) (%Icu)
Magnetic Setting (Times Ampere Rating)
Dimensions
Weight (Max.)
60 Vdc
125 Vdc
B curve
C Curve
D Curve
Width
Height (Box/Box)
Depth
UL 489 C60 (DC)
1
60 Vdc
10
—
75%
—
7 to 14
—
0.71 in. (18 mm)
4.21 in. (107 mm)
3.00 in. (76 mm)
4.4 oz. (136 g)
2
—
10
75%
—
7 to 14
—
1.42 in. (36 mm)
4.21 in. (107 mm)
—
8.7 oz. (271 g)
+
–
13
24
Load
12 in. Min.
2-Pole Wiring
Diagram
Catalog Numbers
Table 10: Catalog Numbers for UL 489 C60 Listed Miniature Circuit Breakers (DC)1
Rating
C Curve
1P, Box/Box
2P, Box/Box
Rating
C Curve
1P, Box/Box
2P, Box/Box
0.5 A
60100
30134
10 A
1A
60101
60135
13 A
1.5 A
60102
60136
15 A
2A
60103
60137
20 A
3A
60104
60138
25 A
4A
60105
60139
30 A
5A
60106
60140
35 A
6A
60107
60141
40 A
7A
60108
60142
50 A
8A
60109
60143
63 A
1 The dc catalog numbers are the same as the UL 489 ac equivalents.
60110
60111
60112
60113
60114
60115
60116
60400
60401
60102
60144
60145
60146
60147
60148
60149
60150
—
—
—
20
© 2002–2008 Schneider Electric All Rights Reserved
03/2008