60132 Datasheet, PDF (5/9 Pages) List of Unclassifed Manufacturers – 60132 Circuit Breaker
Multi 9Â¥ System Catalog
Section 2—UL and CSA Rated Protection Devices
UL 489 Listed 240 Vac C60 Circuit Breakers (AC)
A selected range of Multi-9 circuit breakers rated 240 V are UL 489 Listed. Unlike UL 1077
Supplementary Protectors, these UL 489 circuit breakers can be used for branch circuit protection as
required by the National Electrical Code.
As shown in tables Table 5 and Table 6, the UL 489 Listed products are available in C and D curves.
They include devices ranging from 0.5 to 35 A.
UL 489 Listed Multi 9 C60 Circuit Breakers
1P
2P
3P
03/2008
Table 4: Specifications for UL 489 240 V Listed C60N Circuit Breakers
High Voltage Withstand
6 kV
Connector: Box Lug
Rating
Connection
UL 486A File No. E216919 (Use with Copper Wire Only)
0.5–25 A: 14–4 AWG (2–25 mm2) Cables
Torque to 22 lb-in. (2.48 N•m)
30–35 A: 14–2 AWG (1–35 mm2) Cables
Torque to 31 lb-in. (3.52 N•m)
Connector: Ring Tongue
Use Single UL Listed or CSA Certified Screw dia. 0.2 in. (5 mm)
Insulated Ring Tongue Only
Torque to 18 lb-in. (2.03 N•m)
Max Ring Terminal Width
0.54 in. (14 mm)
Mounting
35 mm DIN rail
Degree of Protection
Case
Terminals
IP40 as per IEC 529
IP20
Calibration
25°C (77°F)
Temperatures
Storage
-40 to 80°C (-40 to 176°F)
Operating
-30 to 70°C (-22 to 158°F)
MN Undervoltage Trip
Plug-On Auxiliary Modules with MX + OF Shunt Trip/Auxiliary Switch
Mechanical Linkage:
OF Auxiliary Switch
SD Alarm Switch
Tropicalization
Treatment 2
Relative Humidity: 95% at 131°F (55°C)
Number of Operating Cycles Electrical (O-C)
6,000 load, 4,000 no-load
See specifications Table 2 for dimensions, weights and interrupting ratings
Standard Features
• Fast closing: Allows increased withstand to the high inrush currents of some loads.
• Trip-free mechanism: Contacts cannot be held in the I-ON position when the C60 circuit breaker is
tripped automatically.
• Positive indication of contact disconnect. Green mechanical indication on front face of circuit
breaker shows that all poles are open.
• C curve: Overcurrent protection for all application types. Magnetic release operates from 7 to 10
times ampere rating (7 to 14 for DC applications).