English
Language : 

60132 Datasheet, PDF (6/9 Pages) List of Unclassifed Manufacturers – 60132 Circuit Breaker
Multi 9Â¥ System Catalog
Section 2—UL and CSA Rated Protection Devices
• D curve: Overcurrent protection for loads with high inrush currents (motors, transformers).
Magnetic release operates between 10 and 14 times ampere rating (no dc rating for D curve).
• Suitable for reverse feeding.
• Allows locking in O-OFF position using padlock attachment.
Connections
Three versions of field wiring connectors are available for the 240 Vac UL 489 Listed devices:
• Box lug, meeting UL 486A requirements
• Ring tongue terminal with 5 mm screw
• Ring Tongue terminals with Fingersafe (IP20) shrouds
The circuit breakers can be ordered with the following combinations of connectors:
• Line terminal box lug/load terminal box lug
• Line terminal ring tongue/load terminal ring tongue (for fingersafe version, add -F suffix to catalog
number)
• Line terminal box lug/load terminal ring tongue
Figure 5: Connection Options for 240 Vac UL 489 Listed Devices
Box Lug
Ring
Tongue
Box Lug
Fingersafe
Ring
Tongue
Box Lug
Ring
Tongue
Ring
Tongue
Standards
• UL 489 Circuit Breaker: File No. E215117
• Single pole 15–20 A is UL Listed as SWD (switching duty).
• 1-, 2-, and 3-pole 15–35 A are HID (high intensity discharge) rated.
• CSA C22.2 No. 5.1 Circuit Breakers: File No. 179014
• IEC 60947-2
• CE Marked
Fingersafe
Ring
Tongue
16
© 2002–2008 Schneider Electric All Rights Reserved
03/2008