Setting
Press the SET button.
Measuring
mode
Press the SET button
and hold for 2 sec. or longer.
Pressure setting
Enter the set value of the
pressure to perform switch
output.
Initial setting
Set the output type, response
time, and display color
switching.
Press the SET button.
Measuring mode
Detects and displays the pressure and
performs switch operations. Other functions
such as the value clear function can be set
according to the application purpose.
Press the SET button.
Initial Setting
Initial setting mode
Press and hold the SET button for 2 seconds or longer.
Display monitor will be per Figure A below, and the switch
will now be in the display color setting mode.
PRESSURE
3. Output type setting
The type of switch output can be set arbitrarily.
While the current output type is displayed, press the
̃DOWN button to switch between normally open
and
normally closed .
PRESSURE
PRESSURE
OUT
Figure A
If the unit specification indicated at the time of ordering is “M”,
the fixed SI unit will be used. If it is Nil, refer to “Unit Switching
Function” on page 16-2-8.
1. Display color setting
Select the color for LCD display.
Press the ̅UP or ̃DOWN button to choose a display color.
PRESSURE
PRESSURE
OUT
ON: Red
PRESSURE
OUT
ON: Green
PRESSURE
OUT
OUT
ON/OFF: Red
ON/OFF: Green
Press the SET button to set the color and proceed to the
operating mode setting.
If the analog output is set, press the ̅UP or ̃DOWN button
and select the desired display color from (Green) or
(Red). Press the SET button to exit this mode and return to
the measuring mode.
2. Operating mode setting
This mode will let you select the switch operating mode.
While the current operating mode is displayed, press the
̅UP or ̃DOWN button to select a newly desired operating
PRESSURE
PRESSURE
OUT
OUT
Hysteresis mode
Hysteresis
(H)
ON
Hysteresis
(H)
ON
OFF
OFF
Window comparator mode
Hysteresis Hysteresis
(H)
(H)
Hysteresis Hysteresis
(H)
(H)
ON
ON
OFF
OFF
P1
n1
(Standard: Factory setting) (Reversed)
P1 P2
(Standard: Factory setting)
n1 n2
(Reversed)
Press the SET button to set the mode and proceed to the
output type setting.
16-2-6
OUT
Normally open
OUT
Normally closed
Press the SET button to set the output type and proceed to
the response time setting.
4. Response time setting
The switch output response time can be set arbitrarily.
Chattering can be prevented with a response time setting.
While the current response time is displayed, press the ̅UP
or ̃DOWN button to select a new response time.
PRESSURE
PRESSURE
PRESSURE
OUT
2.5 ms
OUT
20 ms
PRESSURE
OUT
160 ms
PRESSURE
OUT
640 ms
OUT
1280 ms
Press the SET button to set the response time and proceed
to the auto preset setting.
If the operating mode is the window comparator mode, press
the SET button to return to the measuring mode.
5. Auto preset setting
This function stores the measuring pressure that is set
during the auto preset mode as a basic value.
While the current setting is displayed, press the ̅UP or
̃DOWN button to select it as an auto preset setting.
PRESSURE
PRESSURE
OUT
Manual
OUT
Auto
Press the SET button to set the auto preset and return to the
measuring mode.