English
Language : 

DRP024V060W1BX Datasheet, PDF (8/15 Pages) Delta Electronics, Inc. – Universal AC input voltage range
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1B□
Engineering Data
Output Load De-rating VS Surrounding Air Temperature
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation
> 50°C de-rate power by 2.5% / °C
Note
1. Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2. If the output capacity is not reduced when the
surrounding air temperature > 50°C, the
device may run into Over Temperature
Protection. When activated, the output
voltage will go into bouncing mode and will
recover when the surrounding air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
4. Depending on the surrounding air
temperature and output load delivered by the
power supply, the device can be very hot!
5. If the device has to be mounted in any other
orientation,
please
contact
info@deltapsu.com for more details.
Output Load De-rating VS Input Voltage
 No output power de-rating across the entire
input voltage range
8
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 06)