English
Language : 

DRP024V060W1BX Datasheet, PDF (2/15 Pages) Delta Electronics, Inc. – Universal AC input voltage range
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range*
Input Current
Efficiency at 100% Load
Max Power Dissipation
Max Inrush Current (Cold Start)
Leakage Current
*Safety approval according to IEC/EN/UL 60950-1.
0% load
100% load
100-240Vac
85-264Vac
50-60Hz
47-63Hz
120-375Vdc
< 1.40A @ 115Vac, < 0.80A @ 230Vac
> 90.0% @ 115Vac & 230Vac
< 0.5W @ 115Vac & 230Vac
< 7.4W @ 115Vac & 230Vac
< 20A @ 115Vac, < 35A @ 230Vac
< 1mA @ 240Vac
Output Ratings / Characteristics**
Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD*** (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
24Vdc
24Vdc ± 2%
24-28Vdc
2.50A (continuously operating at 24V)
3.75A (Power Boost for 5 seconds at 24V, refer to the details in
the Functions section)
60W (continuously operating at 24V)
90W (Power Boost for 5 seconds at 24V, refer to the details in
the Functions section)
< 0.5% typ. (@ 85-264Vac input, 100% load)
< 1% typ. (@ 85-264Vac input, 0-100% load)
< 150mVpp
< 100ms @ nominal input (100% load)
< 2,000ms @ nominal input (100% load)
> 20ms @ 115Vac (100% load)
> 125ms @ 230Vac (100% load)
± 5% @ 85-264Vac input, 0-100% load
(Slew Rate: 0.1A/μS, 50% duty cycle @ 50Hz to 1KHz)
8,000µF Max
**For power de-rating from 50°C to 80°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1μF ceramic capacitor & 47μF electrolytic capacitor.
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 06)